When the transformer operates in the power system, it is difficult to avoid some short-circuit events. Depending on the severity of the short-circuit event and the strength of the transformer's anti short-circuit ability, sometimes it is safe and sometimes it is damaged. The damage of a distribution transformer will affect a factory in a short time, while the short-circuit accident of a distribution transformer will affect an urban area, and the replacement is more difficult, and the repair takes 2 3 months. Therefore, improving the short-circuit resistance of power transformer has always been a matter of great concern to the power department, and it is also the main goal of the manufacturing department.
Before the 1990s, there were only four high current laboratories (stations) in Xi'an, Shenyang, Shanghai and Beijing in China. Their facilities are mainly for switching capacity test in the switching industry, but they can also test distribution transformers. Therefore, in the early and mid-1980s, Shenyang
Transformer Research Institute היה אחראי על התכנון המאוחד של sl7 ושל s9-30 שנאי הפצה של 1600KVA / 10kV הישנים. ניסוי האב-טיפוס שהופק על ידי כל מפעל ערכו בדיקות קצרות{12}}במעגלים במעבדות (תחנות) לעיל. 14 sl7 ו-12 S9 ישנים עברו את המבחנים. לאחר הצלחת המבחן, סוג ה-S9 החדש יוצר בניסיון. המנה הראשונה של 37 יחידות עברה את המבחן, ושיעור ההסמכה של הסוג החדש של S9 הגיע ליותר מ-90 אחוזים (Kema בהולנד בדקה שנאי הפצה זרים, עם שיעור הסמכה חד פעמי של 50 אחוז). עד שנת 1996 נבדקו כ-300 שנאי חלוקה במעבדות שונות (תחנות), כולל מסוג S7.
For more than ten years, China has done a lot of short-circuit tests on distribution transformers, and improved each damage condition, so that the qualified rate reaches more than 90 percent , much higher than the foreign qualified rate of 50 percent , which has been confirmed in the actual operation of power grid and achieved gratifying results. It can be said that the basic solution to the short-circuit strength of distribution transformer depends on "practical test", which is a very important experience.
אין בסיס לבדיקת שנאי כוח בסין, ולכן קשה לפתור את התנגדות הקצר-של שנאי כוח. בשנת 1986 אישרה ועדת התכנון הממלכתית את בניית תחנת בדיקה של זרם גבוה שניאנג הושיטאי, שהושאלה על ידי המדינה ואושרה להתייעצות על ידי חברת EDF מצרפת. לאחר שנים רבות של עבודה, השלב הראשון של הפרויקט הסתיים בסוף 1993, נבנתה רשת 220kV והותקנו שני 1200mva / 0 224kv. לאחר קבלתה על ידי ועדת המומחים של המדינה, הוא הופעל בינואר 1994 ומספר רב של בדיקות שנאי חלוקה בוצעו בשנים 1994 ו-1995, לאחר שצברה ניסיון, בדיקת-המעגל הקצר של שנאי כוח 110kV בוצע בשנת 1996.
בדיקת קצר חשמלי של שנאי כוח 110kV
110kV power transformer is the main transformer in China's transmission and distribution system, and its output accounts for about 1 / 5 of the total output of transformer. According to the statistical data from 1995 to 1996, the short-circuit accident of 110kV transformer accounts for 5O percent of the total accident of this level, and shows an upward trend. Therefore, how to improve the short-circuit resistance of this level of power transformer has become the main topic at the Zengcheng conference in Guangdong. It is recognized that the best way is to verify it with short-circuit test.
From 1996 to the first half of 2005, due to the attention of power departments and manufacturing enterprises, More than 60 factories have successively conducted short-circuit tests on 80 110kV power transformers (including 4 from Shenyang Transformer Co., Ltd., 3 from Xinjiang TBEA Co., Ltd., 2 from Nantong AIA Transformer Co., Ltd., 2 from Changzhou transformer factory, 3 from Yunnan Transformer Factory, 2 from Baoding, 3 from Huapeng, etc.) with a pass rate of >96 אחוז. שנאי חלוקה עם קצב הסמכה גבוה מ-10kV.
על מנת לעבור את המבחן הראשון, השקיעו מפעלים אלו משאבים אנושיים וחומריים רבים. בתהליך פיתוח המוצר, הם עשו מאמצים מסוימים בתכנון, תהליך, ייצור וניהול, וזה ללא ספק שיפור גדול לאיכות המקיפה של ארגונים. 28 מתוך 45 המוצרים שנבדקו במחצית הראשונה של 2001 פעלו על רשת החשמל, וזה עם זמן הריצה הקצר ביותר פועל כבר כמה חודשים. ביניהם, מוצר חדש של תחנת המשנה של שניאנג, שנאי 50000kVA / 110kV, פועל כבר יותר מחמש שנים ומתקבל בברכה על ידי המשתמשים. על בסיס קבלת נתוני הבדיקה, מפעלים אלו שיפרו את מבנה עיצוב המוצר. בהתחשב בכך כסטנדרט, הם הוכנסו לייצור המוני והוכנסו לרשת החשמל, כך שלא יהיו תאונות קצרות- בעתיד.
הנתונים הסטטיסטיים של מכון מחקר המתח הגבוה של Wuhan of State Power Corporation ושל China Electric Power Research Institute מ-1995 עד 1999 מראים כי תאונת הקצר של השנאי ירדה מ-50% בעבר ל-40%, כלומר בעיקר בשל שיפור אמינות פעולת המערכת עקב פעולת אצווה הנ"ל של שנאים אמינים במיוחד. יש לומר שתאונת המעגל הקצר- של שנאי 110V נבלמה בתחילה.
יש להרחיב עוד יותר את בדיקת-המעגל הקצר של שנאי 110kV
נכון לעכשיו, ישנם 60 מפעלים המספקים בדרך כלל שנאי כוח של 110V בסין, ורק יותר מ-100 מפעלים ביצעו בדיקות קצרות של שנאי-של 110kV, מהווים כ-55 אחוזים. כמה מפעלים מכינים תנאים לבדיקת-מעגל קצר, הדורשת תמיכה חזקה מהמשתמשים ומאמצת באופן פעיל את המוצרים שנבדקו כדי למלא תפקיד במערכת. מבחינת מפעלי ייצור, עלינו לבצע עבודות מבחינה עיצובית וטכנולוגית, לבצע הכנות חומריות מספקות, לגייס כספים ולהוציאם לפועל. כמו כן, יש לציין כי מפעלים שלא ביצעו בדיקת מעגל קצר-שנאי צריכים לתפוס את הזמן, כדי לא להשפיע על ההזמנה ואף לאבד את הכשרת הייצור.